Chapter 3 – Installation and Wiring

3-15

Table 3.F specifies the srew size needed to secure the green
ground wire of the SMP-3 overload relay to earth ground.

Table 3.F Ground Screw Specifications

Cat. No.

Screw Type

Standard

Metric

193-C1_1, 2, or 3
592-C1_T, A, or C

No. 8

M4

193-C1_4 or 5

592-C1_D or E

1/4”

M6

Figure 3.10 SMP-3 Customer Interfaces

Configuration
DIP Switches

FLC Setting

DIP Switches

A2 Terminal

Manual Reset Button

Communication Port

Remote Reset Port

Status LEDs

Ground Wire

Table 3.G Control Terminal Block Designation

Terminal

Description

10

Out A

20

Out B

30, 40

Normally Closed Contact

50, 60

Power Supply (110-240V AC)

Output A and B output the power supply voltage with respect to terminal 60.

Contact is closed when the SMP-3 overload relay is reset and powered.
Contact is open when the SMP-3 overload relay is unpowered.

Note: The SMP-3 ground wire must be connected to earth
ground.