Chapter 9 – Troubleshooting and Fault Information

9-6

Table 9.A Fault Codes

Fault Description

Number of Flashes

HIM Fault Text

HIM Fault Code

Protection Fault

Reset

Test

1

Trip/Test

F1

Manual

Overload

2

Overload

F2

Auto/ Manual

Phase Loss

3

Phase Loss

F3

Manual

Ground Fault

4

Ground Fault

F4

Manual

Jam/Stall

5

Jam/Stall

F5

Manual

<Min.
Allowable FLC Setting

6

Illegal FLC Set

F6

Manual

Non-volatile Memory Fault

7

Non Vol Memory

F7

Manual

Communications Loss

8

Comm Fault

F8

Manual

The

✓indicates the protection faults.

Note: When the SMP-3 Auto/Manual DIP switch is in the
AUTO position, an overload fault (F2) will automatically reset
after a defined reset time (see Chapter

4

for Reset times). All

other faults must be manually reset, but they can be reset
immediately after the fault occurs.

Note: All protection faults are non-volatile. If power is
removed from the SMP-3 overload relay after a protection fault
occurs but before the fault is cleared, the SMP-3 overload relay
will power up in a faulted state once power is re-applied.