Rockwell Automation 193 193-5.0: Bulletin 913/592 SMP-3 Solid-State Overload Relay User Manual
Page 24

Chapter 3 – Installation and Wiring
3-14
Table 3.E Wire Size and Torque Specifications (Continued)
Cat
Power Terminals
Control Terminals
Cat. No.
XXX=
Current
Ra ge
Min. Wire Capacity
Max. Wire Capacity
Torque
Min. Wire Capacity
Max. Wire Capacity
Torque
(XXX=
592 or
193)
Current
Range
(A)
Metric
(mm
2
)
AWG
Metric
(mm
2
)
AWG
Lug
Nm
(Lb-in)
Wire
Nm
(Lb-in)
Metric
(mm
2
)
AWG
Metric
(mm
2
)
AWG
Nm
(Lb-in)
193-C1_2
193-C1_3
592-C1_C
0.7-75
2.5
#14
35
#2
–
4
(35)
0.5
#22
(2) 2.5
(2) #14
0.8
(7)
193-C1_4
592-C1_D
20-180
10
#8
50
#1/0
17
(150)
17
(150)
0.5
#22
(2) 2.5
(2) #14
0.8
(7)
193-C1_5
592-C1_E
20-180
16
#6
120
#4/0
31
(275)
31
(275)
0.5
#22
(2) 2.5
(2) #14
0.8
(7)
193-C1N6
592-C1NF
592-C1NG
70-304
25
#4
240
500MCM
45
(400)
42
(375)
0.5
#22
(2) 2.5
(2) #14
0.8
(7)
193-C1P6
592-C1PF
592-C1PG
100-414
50
(2) #1/0
(2) 185
(2)
350MCM
45
(400)
31
(275)
0.5
#22
(2) 2.5
(2) #14
0.8
(7)
193-C1R6
592-C1RF
592-C1RG
140-608
50
(2) #1/0
(2) 240
(2)
500MCM
45
(400)
31
(275)
0.5
#22
(2) 2.5
(2) #14
0.8
(7)
193-NX15
300:5
2.5
#14
10
#8
–
1.8 (16)
0.5
#22
(2) 2.5
(2) #14
0.8 (7)
193-NX16
400:5
2.5
#14
10
#8
–
1.8 (16)
0.5
#22
(2) 2.5
(2) #14
0.8 (7)
193-NX17
630:5
2.5
#14
10
#8
–
1.8 (16)
0.5
#22
(2) 2.5
(2) #14
0.8 (7)