Table 3.E Wire Size and Torque Specifications (Continued)

Cat

Power Terminals

Control Terminals

Cat. No.

XXX=

Current

Ra ge

Min. Wire Capacity

Max. Wire Capacity

Torque

Min. Wire Capacity

Max. Wire Capacity

Torque

(XXX=
592 or

193)

Current

Range

(A)

Metric

(mm

2

)

AWG

Metric

(mm

2

)

AWG

Lug

Nm

(Lb-in)

Wire

Nm

(Lb-in)

Metric

(mm

2

)

AWG

Metric

(mm

2

)

AWG

Nm

(Lb-in)

193-C1_2
193-C1_3

592-C1_C

0.7-75

2.5

#14

35

#2

4

(35)

0.5

#22

(2) 2.5

(2) #14

0.8

(7)

193-C1_4

592-C1_D

20-180

10

#8

50

#1/0

17

(150)

17

(150)

0.5

#22

(2) 2.5

(2) #14

0.8

(7)

193-C1_5

592-C1_E

20-180

16

#6

120

#4/0

31

(275)

31

(275)

0.5

#22

(2) 2.5

(2) #14

0.8

(7)

193-C1N6
592-C1NF

592-C1NG

70-304

25

#4

240

500MCM

45

(400)

42

(375)

0.5

#22

(2) 2.5

(2) #14

0.8

(7)

193-C1P6
592-C1PF

592-C1PG

100-414

50

(2) #1/0

(2) 185

(2)

350MCM

45

(400)

31

(275)

0.5

#22

(2) 2.5

(2) #14

0.8

(7)

193-C1R6
592-C1RF

592-C1RG

140-608

50

(2) #1/0

(2) 240

(2)

500MCM

45

(400)

31

(275)

0.5

#22

(2) 2.5

(2) #14

0.8

(7)

193-NX15

300:5

2.5

#14

10

#8

1.8 (16)

0.5

#22

(2) 2.5

(2) #14

0.8 (7)

193-NX16

400:5

2.5

#14

10

#8

1.8 (16)

0.5

#22

(2) 2.5

(2) #14

0.8 (7)

193-NX17

630:5

2.5

#14

10

#8

1.8 (16)

0.5

#22

(2) 2.5

(2) #14

0.8 (7)

Advertising