Chapter 4 – Functional Description

4-5

Figure 4.4 SMP-3 Trip Curves – Class 30

Approximate trip time
for 3-phase balanced condi-
tion from cold start.

Approximate trip time
for 3-phase balanced condi-
tion from hot start.

Multiples of Full Load Current

Approximate T

rip

T

ime

(sec.)

1.0

10.0

100.0

1000.0

10000.0

1

10

2

3

9

8

7

6

5

4

The following figure illustrates the time-current characteristics
of the SMP-3 overload relay after the auto-reset time has
expired and the SMP-3 overload relay is reset.

Figure 4.5 SMP-3Trip Curve after Auto Restart

1000%

100%

0

1

10

100

1000

100000

Percent Full Load Current Setting

Seconds

Class 10

Class 15

Class 20

Class 30

Auto Reset Times:

Class 10 = 90s
Class 15 = 135s
Class 20 = 180s
Class 30 = 270s