Chapter 3 – Installation and Wiring

3-37

FLC SETTING FOR APPLICATIONS IN USA AND CANADA

Motors with a Service Factor of 1.15 or greater: set the full load
current to the nearest value of the motor current taken from the
motor nameplate.

Motors with Service Factor of less than 1.15: set the full load
current to the nearest value of 90% of the motor current taken
from the motor nameplate.

Wye-Delta (Y

) Applications (relay carrying motor phase current):

Follow the applicable service factor instruction, except divide
the motor nameplate full load current amperes by 1.73.

FLC SETTINGS FOR APPLICATIONS OUTSIDE USA AND
CANADA

Maximum Continuous Rated (MCR) Motors: Set the full load
current to the nearest value of the motor current taken from the
motor nameplate.

Star-Delta (Y

) Applications (relay carrying motor phase current):

Follow the above MCR instructions, except divide the motor
nameplate full load current amperes by 1.73.