Short circuit ratings – Rockwell Automation 193 193-5.0: Bulletin 913/592 SMP-3 Solid-State Overload Relay User Manual
Page 23

Chapter 3 – Installation and Wiring
3-13
Short Circuit Ratings
The SMP-3 overload relay is suitable for use on a circuit
capable of delivering not more than the RMS symmetrical
amperes, 600 volts maximum, as listed in Table 3.D .
Table 3.D SMP-3 Short Circuit Ratings
Cat. No.
Maximum Available
Amperes
Maximum
Voltage
193-C1_1, -C1_T
5,000A
600V
193-C1_2, _3, _A, _C, _4, _5,
_D, _E,
10,000A
600V
193-C1N6
18,000A
600V
193-C1P6
30,000A
600V
193-C1R6
42,000A
600V
Select the motor branch circuit protection that complies with
The National Electrical Code and any other governing regional
or local codes.
Table 3.E Wire Size and Torque Specifications
Power Terminals
Control Terminals
Cat
Current
Ra ge
Min. Wire Capacity
Max. Wire Capacity
Torque
Min. Wire Capacity
Max. Wire Capacity
Torque
Cat. No.
Current
Range
(A)
Metric
(mm
2
)
AWG
Metric
(mm
2
)
AWG
Lug
Nm
(Lb-in)
Wire
Nm
(Lb-in)
Metric
(mm
2
)
AWG
Metric
(mm
2
)
AWG
Nm
(Lb-in)
193-C1_1
592-C1_T
0.7-37
2.5
#14
10
#8
–
1.8
(16)
0.5
#22
(2) 2.5
(2) #14
0.8
(7)
592-C1_A
0.7-75
2.5
#14
10
#8
–
2.3
(20)
0.5
#22
(2) 2.5
(2) #14
0.8
(7)