Chapter 3 – Installation and Wiring

3-13

Short Circuit Ratings

The SMP-3 overload relay is suitable for use on a circuit
capable of delivering not more than the RMS symmetrical
amperes, 600 volts maximum, as listed in Table 3.D .

Table 3.D SMP-3 Short Circuit Ratings

Cat. No.

Maximum Available

Amperes

Maximum

Voltage

193-C1_1, -C1_T

5,000A

600V

193-C1_2, _3, _A, _C, _4, _5,

_D, _E,

10,000A

600V

193-C1N6

18,000A

600V

193-C1P6

30,000A

600V

193-C1R6

42,000A

600V

Select the motor branch circuit protection that complies with
The National Electrical Code and any other governing regional
or local codes.

Table 3.E Wire Size and Torque Specifications

Power Terminals

Control Terminals

Cat

Current

Ra ge

Min. Wire Capacity

Max. Wire Capacity

Torque

Min. Wire Capacity

Max. Wire Capacity

Torque

Cat. No.

Current

Range

(A)

Metric

(mm

2

)

AWG

Metric

(mm

2

)

AWG

Lug

Nm

(Lb-in)

Wire

Nm

(Lb-in)

Metric

(mm

2

)

AWG

Metric

(mm

2

)

AWG

Nm

(Lb-in)

193-C1_1
592-C1_T

0.7-37

2.5

#14

10

#8

1.8

(16)

0.5

#22

(2) 2.5

(2) #14

0.8

(7)

592-C1_A

0.7-75

2.5

#14

10

#8

2.3

(20)

0.5

#22

(2) 2.5

(2) #14

0.8

(7)