Chapter 9 – Troubleshooting and Fault Information

9-4

Failure Type

Action to Take

General Problem

Communication

The communication link between the
SMP-3 and an adapter does not appear to
be functioning.

1. Check the HIM display (if applicable). If the display appears to be cycling between menus:

a. Check the communication connection per the procedure described in Table 9.B for a

Comm Fault.

b. Induce a Test fault on the SMP-3 overload relay. If the SMP-3 overload relay does not

trip, consult the factory.

If the display is de-energized:
a. Check the communication connection per the procedure described in Table 9.B for a

Comm Fault.

b. Follow the Power-up Failure troubleshooting procedure previously described.

2. Check the SCANport status LED (if applicable) on the Communication Module. If the LED is

“On”:
a. Check the non-SCANport communication connections (i.e., RIO, DeviceNet).
If the LED is “Off”:
a. Check the communication connection per the procedure described in Table 9.B for a

Comm Fault.

b. Induce a Test fault on the SMP-3 overload relay. If the SMP-3 overload relay does not

trip, consult the factory.

3. Check the Logic Mask Parameter. Refer to Chapter 8 for programming instructions.

Communication

Comm Fault exists.

Refer to Table 9.B for instructions regarding how to correct Comm faults.