Troubleshooting with the indicators, Chapter, Diagnostic indicators – Rockwell Automation 1769-ADN Compact I/O 1769-ADN DeviceNet Adapter User Manual

Page 111

Advertising
background image

1

Publication 1769-UM001B-EN-P - October 2002

Chapter

5

Troubleshooting with the Indicators

Read this chapter to familiarize yourself with the diagnostic indicators
and their meanings.

Diagnostic Indicators

LED Indication

Meaning

Module Status (MS)

OFF

No power

Flashing GRN/OFF

On-line but configuration missing

Solid GRN

Device operational

Flashing RED/OFF

Recoverable fault

• configuration incorrect
• duplicate mac id (node address) check failed
• node address switch changed
• main program checksum failed
• configured I/O size too large

Solid RED

Unrecoverable fault

• terminator/end cap missing
• connector/cable between modules missing/not connected
• bad configuration memory
• watchdog tripped

Comm Adapter

MS

IO

NS

DIAG

I/O Status Indicator

42128

Module Status Indicator

Diagnostic Status Indicator

Network Status Indicator