Chapter
5
Troubleshooting with the Indicators
Read this chapter to familiarize yourself with the diagnostic indicators
and their meanings.
Diagnostic Indicators
LED Indication
Meaning
Module Status (MS)
OFF
No power
Flashing GRN/OFF
On-line but configuration missing
Solid GRN
Device operational
Flashing RED/OFF
Recoverable fault
• configuration incorrect
• duplicate mac id (node address) check failed
• node address switch changed
• main program checksum failed
• configured I/O size too large
Solid RED
Unrecoverable fault
• terminator/end cap missing
• connector/cable between modules missing/not connected
• bad configuration memory
• watchdog tripped
Comm Adapter
MS
IO
NS
DIAG