Publication 1769-UM001B-EN-P - October 2002

2-8 How Communication Takes Place and I/O Image Table Mapping

1769-OA16 100 to 240V AC
Solid State Output Module
(16 Point)

Output Data File

Data output bits are turned on or off using the bit positions in Word 0.

1 = output on

0 = output off

Example: To turn on bit position 12, type 1 in Word 0, Bit 12.

For each module, slot x, word 0 in the output data file contains the
control program’s directed state of the discrete output points.

Output Module’s Input Data File

For each module, slot x, input data file word 0 contains the state of
the module’s output data (output data echo) file word 0. During
normal operation, these input bits represent the logic state that the
outputs are directed to by the control program. They are also
dependent upon the:

• Program Mode configuration (if supported by the controller)
• The Fault Mode configuration (if supported by the controller)

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

w

w

w

w

w

w

w

w

w

w

w

w

w

w

w

w

w = write

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

r

r

r

r

r

r

r

r

r

r

r

r

r

r

r

r

r = read

IMPORTANT

The output module’s input data file reflects the
output data echo of the module, not necessarily the
electrical state of the output terminals. It does not
reflect shorted or open outputs.

It is important to use this input word if the controller
adapter supports the Program Mode or Fault Mode
function, and if it is configured to use them.