Configuring Your Compact I/O Series A DeviceNet Adapter 3-19

RSNetworx uses this information when it performs an audit of
the configuration with regards to +24V requirements.

Note: This parameter is not saved in the Series A 1769-ADN
adapter. The default is that the 1769 power supply is supplying
the +24V for this module any time you perform an upload from
the 1769-ADN adapter. Therefore, when online refer to Auditing
the Configuration on page 3-20.

9. To change the default for when communications fail during

program mode for each channel, choose to leave the outputs in
program mode or to change the outputs to fault mode.

10. If desired, choose Set for I/O Only to automatically modify the

input/output sizes to real time size defaults and other
configurations to their default values.

11. If desired, choose Data Description to view the definitions of

each input and output word.

12. To remove specific words/functions, uncheck the appropriate

box and choose OK.

13. To apply the specific words/functions, check the appropriate

box and choose OK.

14. Once you’ve finished making your changes, you may choose

OK from the I/O Module screen to return to the Bank
Configuration screen.