Rockwell Automation 1769-ADN Compact I/O 1769-ADN DeviceNet Adapter User Manual

Page 98

Advertising
background image

Publication 1769-UM001B-EN-P - October 2002

4-22 Configuring Your Compact I/O Series B DeviceNet Adapter

2. To assign the module to a different bank, enter the bank number

in the Bank field.

3. From the Advanced Parameters tab, you can configure editable

parameters by selecting from the pull-down menus or directly
typing in the value.

Exact Match: The programmed module type (e.g. 1769-IA16)

and the revision must match exactly with the actual module.

Compatible Module: The programmed module type must

match the actual module, but the revision of the actual
module can be equal or greater than the programmed
revision.

Disable: Any module may be used as a replacement.

Refer to the Comparison Feature section on page 4-29 for an
explanation on the use of this field.

TIP

To save time, assign the bank numbers to the
first (left-most) modules in each bank, starting
with bank one. The software ripples the bank
modification down the list when you close the
module’s property window.

You can configure the Input
Data Size parameter to No
Input Data, Status Bits (1
Word), Overrange/Underrange
Bits (2 Words), Channel 0
Output Echo (3 Words), or
Channel 1 Output Echo (4
Words).

You can configure the
Electronic Keying
parameter to Disable
Keying, Exact Match, or
Compatible Module.

You can configure the Output
Data Size parameter to No
Output Data, Channel 0
Output Data (1 Word), or
Channel 1 Output Data (2
Words).

Advertising