3-4 Configuring Your Compact I/O Series A DeviceNet Adapter
2. Continue to list your devices down the left column and continue
at the top right column if necessary.
Note: To limit the need to reconfigure, make sure you
understand the Configuration Rules for the Series A Adapter on
page 3-7.
Notice that only I/O modules are assigned Slot numbers.
3. Once you’ve listed all of the devices for Bank 1, go on to Bank 2
if necessary.
Note: A second I/O bank may be necessary if your bank 1
power supply has an insufficient power budget for the I/O
modules required for your application.
Note: Make sure your bank-to-bank expansion cable (e.g.
1769-CRR1) is in the last component of bank 1.