Explicit Messaging Application Examples B-9

The following correlates the CIP Generic message terminology with
DeviceNet command terminology and illustrates the values needed
specifically for the Get 1769 I/O Configuration Size message:

Should a configuration error occur, the Logix5550 controller’s MSG
instruction will display the error as a hex code as well as in words.
The error code is two bytes, where one byte is the General Error Code
and the other byte is the Extended Error Code.

If the Extended Error Code is 00ff hexadecimal, the responding object
has no additional information to specify. For example, if we make the
third, fourth, fifth, or sixth word of the configuration portion in the Set
I/O Module Configuration command 0 rather than 1862 hexadecimal,
the MSG instruction will set the error bit and display an Error Code of
0009 hexadecimal with an Extended Error Code of 00ff hexadecimal.
The error description is “Parameter error in module configuration”.

Values (Hexadecimal)

DeviceNet Terminology

CIP Generic Terminology

10

Service

1

Service Code

30c

Class

2

Object Type

10 (decimal)

Instance

3

Object ID

1a

Attribute

4

Object Attribute

8304

First word of the 1769-OF2 configuration file

5

8304

Second word of the 1769-OF2 configuration file

5

1862

Third word of the 1769-OF2 configuration file

5

1862

Fourth word of the 1769-OF2 configuration file

5

1862

Fifth word of the 1769-OF2 configuration file

5

1862

Sixth word of the 1769-OF2 configuration file

5

0000

Seventh word of the 1769-OF2 configuration file

5

0000

Eighth word of the 1769-OF2 configuration file

5

1

Service specifies the type of request being delivered. “10” hexadecimal is a “Single Parameter Write”.

2

Class specifies the desired DeviceNet class. “30c” hexadecimal is the class code for the object representing

1769 I/O.

3

Instance represents the slot number of the I/O module for which we want to set the configuration.

“10” decimal in this example is the analog output module in slot 10.

4

Attribute identifies the specific characteristics of the object towards which the transaction is directed.

“1a” hexadecimal means configuration data.

5

Configuration data is 8 words in length, although only 6 words contain actual configuration data. The last

two words must be included, but must be 0000 hexadecimal. The actual configuration data information may

be found in the Compact I/O Analog Module User Manual, publication 1769-6.0. Chapter 5 of that

publication shows the layout of the six configuration words for the 1769-OF2 module.

The first two words of the configuration file configure channels 0 and 1 respectively for such features as the

output data format (Raw/Proportional Data for this example) and output type (4-20mA for the example).

The next four words are values for the two channels in the event the controlling processor faults or is placed

into the Program mode. For this example, these four values must be in the range of 6241 or 31207 decimal

(1862 to 79E7 hexadecimal), which represents 4-20mA. Any values out of this range will result in a

configuration error.