Rockwell Automation 1769-ADN Compact I/O 1769-ADN DeviceNet Adapter User Manual

Page 112

Advertising
background image

Publication 1769-UM001B-EN-P - October 2002

5-2 Troubleshooting with the Indicators

Network Status (NS)

OFF

No DeviceNet power or no network access

Flashing GRN/OFF

On-line but not connected

Solid GRN

On-line and connected

Flashing RED/OFF

Connection time-out

Solid RED

Critical network failure

I/O Status (IO)

OFF

No power or outputs off

Flashing GRN/OFF

Idle/program mode - one or more I/O modules in Idle Mode

Solid GRN

Device operational - all I/O modules in Run Mode

Flashing RED/OFF

Recoverable fault - one or more I/O modules may be in
Fault Mode

Solid RED

Unrecoverable fault - one or more I/O modules may be in
Fault Mode

Diagnostic Status (DIAG)

OFF

No power or no diagnostics running

Flashing Amber

Main Program detected an error - number of flashes indicates
the error

Flashing Green/OFF

Diagnostic self-tests are in progress

Flashing RED/OFF

Diagnostics found error - number of flashes indicates which test
failed

• One flash- RAM test failed
• Two flashes- Boot program checksum failed
• Three flashes- Main program checksum failed
• Four flashes- Configuration checksum failed
• Five flashes- Access to program or configuration failed
• Six flashes- Backplane power fault (Series B only)

Solid RED

Watchdog tripped

LED Indication

Meaning

Advertising