Input data – Rockwell Automation 1769-ADN Compact I/O 1769-ADN DeviceNet Adapter User Manual

Page 30

Advertising
background image

Publication 1769-UM001B-EN-P - October 2002

2-6 How Communication Takes Place and I/O Image Table Mapping

1769-IF4 (Series A and B)
Analog Current/Voltage
Input Module (4 Channel)

Input Data

For each 1769-IF4 input module, input data words 0-3 contain the
analog value of the inputs. Word 4 and 5 contain analog status and
error information.

1769-IM12 240V AC Input
Module (12 Point)

Input Data

For each 1769-IM12 input module, input data word 0 contains the
current state of the field input points. Bits 12 to 15 are not used.

1769-IQ16 24V DC
Sink/Source Input Module
(16 Point)

Input Data

For each 1769-IQ16 input module, input data word 0 contains the
current state of the field input points.

Wo

rd

Bit Position

15

14 13 12 11 10

9

8

7

6

5

4

3

2

1

0

0

SGN

Analog Input Data Channel 0

1

SGN

Analog Input Data Channel 1

2

SGN

Analog Input Data Channel 2

3

SGN

Analog Input Data Channel 3

4

Not Used

S3 S2 S1 S0

5

U0

O0 U1 O1 U2 O2 U3 O3

Set to 0

SGN= sign bit in two’s format
Sx = general status bit for channels 0 through 3. This bit is set (1) when an error (over- or

under-range) exists for that channel.

Ux = under-range flag bits for channels 0 through 3. These bits can be used in the control

program for error detection.

Ox = over-range flag bits for channels 0 through 3. These bits can be used in the control

program for error detection.

Wo

rd

Bit Position

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

0

0

0

0

0

0

r

r

r

r

r

r

r

r

r

r

r

r

r = read

Wo

rd

Bit Position

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

0

0

r

r

r

r

r

r

r

r

r

r

r

r

r

r

r

r

r = read