Configuring Your Compact I/O Series B DeviceNet Adapter 4-5

4. Make sure that the last bank of the node is an end

cap/terminator (1769-ECR or 1769-ECL).

For information on 1769 bus configuration rules, refer to
Configuration Rules for Series B Adapters on page 4-6.

5. Choose Apply to be sure that your system passes the electrical

audit.

6. After defining the devices on this 1769-ADN node, refer to the

relevant sections on pages 4-9 to 4-25 to configure each 1769
I/O module.

7. Once all of the I/O modules are configured, choose OK.

8. From the File menu, choose Save.

9. Go on-line.

10. Select the adapter you wish to modify and download your

changes to make them go into affect.

TIP

If your selected adapter is in a scanner’s
scanlist, you may have to deactivate it’s entry
in the scanlist in order for the download to
succeed with no errors. If no input or output
sizes were changed, deactivating the adapter’s
scanlist entry is usually not necessary.