Rockwell Automation 1771-ASB/E Remote I/O Adapter User Manual User Manual

Page 18

Advertising
background image

2–4

Installing Your Module

Publication 1771-UM001A-US-P - February 2000

link response - unrestricted or series B emulation.

Certain scanner modules with multiple communication ports
require a delay in the link turnaround time to allow the central
processing unit (CPU) in the scanner sufficient time to service
all communication ports. Without this delay, some incoming
information may be missed while the scanner is servicing
another port. This results in multiple communication retries.
To provide the necessary delay, set the link response switch
(position 5, switch S2) to the ON position.

Scanner modules which require a delay are:

Programmable Controller

Scanner Module

PLCĆ2

1772ĆSD2
1775ĆS4A

PLCĆ3

1775ĆS4B

1775ĆS5

PLCĆ3/10

1775ĆSR5

PLCĆ3/10

1775ĆSR

noise immunity – enables backplane retries to occur when
noise is detected on the I/O rack backplane. This feature is
enabled when the switch is off. Do not use this switch position
as a substitute for improper noise suppression.

Refer to the Table below for Figure and page numbers of switch
settings for each processor family.

S1 and S2 Switch Settings for:

Refer to:

PLCĆ2 family processor

Figure2.4, page2-5

PLCĆ3 family processor

Figure2.5, page2-6

PLCĆ5 family, SLC and ControlLogix processors

without complementary I/O

Figure2.6, page2-7

PLCĆ5 family, SLC and ControlLogix processor with

complementary I/O

Figure2.7, page2-8