Settings for 1771–AS and 1771–ASB Series A, B, C and D Remote I/O Adapters

B–4

Publication 1771ĆUM001A-US-P - February 2000

FigureB.4

Module Switch Assembly Settings for 1771-AS, -ASB series

A and B Adapter for PLC-2 Family Processors

1 2 3 4 5 6 7 8

O

N
O

F

F

O

N
O

F

F

1 2 3 4

First I/O group number

(Table B.A)

I/O rack number

(Table B.A)

Always OFF

Address Switch Assembly

(SW-1)

Switch Assembly

(SW-2)

SD - always OFF

SD2 - without complementary I/O - always OFF

SD2 - with complementary I/O -

ON - Primary chassis

OFF - Complementary chassis

Pressed in at top

Closed (ON)

Pressed in at bottom

Open (OFF)

SD - always ON

SD2 - without complementary I/O

- always ON

SD2 - with complementary I/O -

ON - Primary chassis

OFF - Complementary chassis

Always ON

10819-I

Maximum I/O Rack Distance

ON - 10,000 cable ft. max. (57.6K baud)

OFF - 5,000 cable ft. max. (115.2K baud)

TableB.A

I/O Rack Selection for PLC-2 Family Processors

I/O Rack

Number

Switch Selections

4

5

6

First I/O Group

Number

Switch Selections

7

8

1

On

On

On

0

On

On

2

On

On

Off

2

On

Off

3

On

Off

On

4

Off

On

4

On

Off

Off

6

Off

Off

5

Off

On

On

6

Off

On

Off

7

Off

Off

On