2–7

Installing Your Module

Publication 1771-UM001A-US-P - February 2000

Figure 2.6

Module Switch Assembly Settings for PLCĆ5 Family, SLC

and ControlLogix Processors Without Complementary I/O

1 2 3 4 5 6 7 8

First I/O group number

(Table 2.C)

I/O rack number

(Table 2.C)

Address Switch Assembly

(S1)

Switch Assembly

(S2)

1 2 3 4

5 6

Link Response Ć ON for series B emulation

OFF for unrestricted

Scan Ć ON for all but last 4 slots

OFF for all slots

Always OFF

10800ĆI

Switch Position

1

2

ON OFF 57.6K Baud Ć 10,000ft

OFF OFF 115.2K Baud Ć 5,000ft

ON ON

Not Used

Maximum I/O

chassis distance (see note)

OFF ON

230.4K Baud Ć 2,500ft

Note: PLCĆ5/15 and 5/25 processors operate

at 57.6K baud only.

Pressed in at top

(ON)

Pressed in at bottom

(OFF)

Off

(ON)

(OFF)

(ON)

(OFF)

OPEN

OPEN

Table 2.C

I/O Rack Selection for PLCĆ5 Family Processors

without Complementary I/O

Rack

#

Switch Setting

1

2

3

4

5

6

Rack

#

Switch Setting

1

2

3

4

5

6

1st I/O

Group

Number

Switch

Selections

7

8

00

On On On On On On

20

On Off On On On On

0

On

On

01

On On On On On Off

21

On Off On On On Off

2

On

Off

02

On On On On Off On

22

On Off On On Off On

4

Off

On

03

On On On On Off Off

23

On Off On On Off Off

6

Off

Off

04

On On On Off On On

24

On Off On Off On On

05

On On On Off On Off

25

On Off On Off On Off

06

On On On Off Off On

26

On Off On Off Off On

07

On On On Off Off Off

27

On Off On Off Off Off

10

On On Off On On On

30

On Off Off On On On

11

On On Off On On Off

31

On Off Off On On Off

12

On On Off On Off On

32

On Off Off On Off On

13

On On Off On Off Off

33

On Off Off On Off Off

14

On On Off Off On On

34

On Off Off Off On On

15

On On Off Off On Off

35

On Off Off Off On Off

16

On On Off Off Off On

36

On Off Off Off Off On

17

On On Off Off Off Off

37

On Off Off Off Off Off

PLCĆ5/11 processors can scan rack 03.

PLCĆ5/15 and PLCĆ5/20 processors can scan racks 01Ć03.

PLCĆ5/25 and PLCĆ5/30 processors can scan racks 01Ć07.

PLCĆ5/40 and PLCĆ5/40L processors can scan racks 01Ć17.

PLCĆ5/60 and PLCĆ5/60L processors can scan racks 01Ć27.

PLCĆ5/250 processors can scan racks 0Ć37.