Settings for 1771–AS and 1771–ASB Series A, B, C and D Remote I/O Adapters

B–14

Publication 1771ĆUM001A-US-P - February 2000

Figure B.16

I/O Chassis Backplane Switch Assembly Settings for

1771-ASB series C and D Remote Adapter Module in PLCĆ5

Family, SLC and ControlLogix Processor System

Processor Restart Lockout Ć

When ON, processor can restart I/O chassis

When OFF, I/O chassis must be restarted at the chassis.

Last State Switch Ć

When ON, outputs of this chassis remain in last state.

When OFF, outputs of this I/O chassis are deenergized

when a fault is detected.

Always OFF

10802ĆI

ATTENTION: Set switch1 to the OFF position

to deenergize outputs wired to this chassis when a

fault is detected. If switch1 is set to the ON

position, outputs connected to this chassis remain

in their last state when a fault occurs and machine

motion may continue after fault detection.

O

O

12

34

56

78

N

F

F

OFF

ON

You select 1/2Ćslot addressing

ON

OFF

You select 1Ćslot addressing

OFF

OFF

You select 2Ćslot addressing

ON

ON

Not allowed

Addressing Switches

5

6

Last Chassis Switch Ć

ON Ć Chassis does not contain the highest numĆ

bered I/O group for the associated rack number

OFF Ć Chassis does contain the highest numbered

I/O group for the associated rack number

If you have only a primary chassis, set this

switchto OFF.

If you have both primary and complementary

chassis, set the primary chassis to ON and the

complementary chassis to OFF.

Figure B.17

I/O Chassis Backplane Switch Assembly Settings for

1771-ASB series C and D Remote Adapter Module in PLCĆ5

Family, SLC and ControlLogix Processor Systems in

Remote Configuration

Processor Restart Lockout Ć

When ON, processor can restart I/O chassis

When OFF, I/O chassis must be restarted at the chassis.

Last State Switch Ć

When ON, outputs of this chassis remain in last state.

When OFF, outputs of this I/O chassis are deenergized

when a fault is detected.

Always OFF

10802ĆI

O

O

12

3
456

7
8

N

F

F

OFF

ON

You select 1/2Ćslot addressing

ON

OFF

You select 1Ćslot addressing

OFF

OFF

You select 2Ćslot addressing

ON

ON

Not allowed

Addressing Switches

5

6

Always OFF

ATTENTION: If switch1 is set to the ON

position, outputs connected to this chassis

remain in their last state when a fault occurs

and machine motion may continue after fault

detection. We recommend that you set switch 1

to the OFF position to deenergize outputs wired

to this chassis when a fault is detected.