2–10

Installing Your Module

Publication 1771-UM001A-US-P - February 2000

Figure 2.9

I/O Chassis Backplane Switch Assembly Settings for

Remote Adapter Module in PLCĆ3 Family Processor System

Processor Restart Lockout Ć

When ON, processor can restart I/O chassis

When OFF, I/O chassis must be restarted at the chassis.

Last State Switch Ć

When ON, outputs of this chassis remain in last state.

When OFF, outputs of this I/O chassis are deenergized

when a fault is detected.

Always OFF

10802ĆI

ATTENTION: Set switch 1 to the OFF position

to deenergize outputs wired to this chassis when

a fault is detected. If switch 1 is set to the ON

position, outputs connected to this chassis remain

in their last state when a fault occurs and machine

motion may continue after fault detection.

O

O

12

34

56

78

N

F

F

OFF

ON

You select 1/2Ćslot addressing

ON

OFF

You select 1Ćslot addressing

OFF

OFF

You select 2Ćslot addressing

ON

ON

Not allowed

Addressing Switches

5

6

1771ĆA1/A1B chassis in PLCĆ3 Backup

ON Ć If any 1771ĆA1/A1B chassis contains

starting I/O group 0 with 2Ćslot addressing

and the PLCĆ3 is configured in backup mode.

OFF Ć All other times.

Figure 2.10

I/O Chassis Backplane Switch Assembly Settings for

Remote Adapter Module in PLCĆ5 Family Processor System

Processor Restart Lockout Ć

When ON, processor can restart I/O chassis

When OFF, I/O chassis must be restarted at the chassis.

Last State Switch Ć

When ON, outputs of this chassis remain in last state.

When OFF, outputs of this I/O chassis are deenergized

when a fault is detected.

Always OFF

10802ĆI

ATTENTION: Set switch 1 to the OFF position

to deenergize outputs wired to this chassis when a

fault is detected. If switch 1 is set to the ON

position, outputs connected to this chassis remain

in their last state when a fault occurs and machine

motion may continue after fault detection.

O

O

12

34

56

78

N

F

F

OFF

ON

You select 1/2Ćslot addressing

ON

OFF

You select 1Ćslot addressing

OFF

OFF

You select 2Ćslot addressing

ON

ON

Not allowed

Addressing Switches

5

6

Last Chassis Switch Ć

ON Ć Chassis does not contain the highest numĆ

bered I/O group for the associated rack number

OFF Ć Chassis does contain the highest numbered

I/O group for the associated rack number

If you haveonly a primary chassis, set this

switch to OFF.

If you have both primary and complementary

chassis, set the primary chassis to ON and the

complementary chassis to OFF.