Rockwell Automation 1771-ASB/E Remote I/O Adapter User Manual User Manual
Page 22

2–8
Installing Your Module
Publication 1771-UM001A-US-P - February 2000
Figure 2.7
Module Switch Assembly Settings for PLCĆ5 Family, SLC
and ControlLogix Processors With Complementary I/O
1 2 3 4 5 6 7 8
First I/O group number
(Table 2.D)
I/O rack number
(Table 2.D)
Address Switch Assembly
(S1)
Switch Assembly
(S2)
Pressed in at top
(ON)
Pressed in at bottom
(OFF)
Always ON
ON Ć Primary chassis
OFF Ć Complementary chassis
ON Ć Primary chassis
OFF Ć Complementary chassis
1 2 3 4
5 6
Link Response Ć ON for series B emulation
Scan Ć ON for all but last 4 slots
OFF for all slots
OFF for unrestricted
10801ĆI
Switch Position
1
2
ON OFF 57.6K Baud Ć 10,000ft
OFF OFF 115.2K Baud Ć 5,000ft
ON ON
Not Used
Maximum I/O
chassis distance (see note)
OFF ON
230.4K Baud Ć 2,500ft
Note: PLCĆ5/15 and 5/25 processors operate at 57.6K
baud only.
Off
(ON)
(OFF)
(ON)
(OFF)
OPEN
OPEN
Table 2.D
I/O Rack Selection for PLCĆ5 Family Processors with
Complementary I/O
I/O
Rack #
Switch
1
2
3
4
5
6
1st I/O Group
Number
Switch Selections
7
8
01
On
On
On
On
On
Off
0
On
On
02
On
On
On
On
Off
On
2
On
Off
03
On
On
On
On
Off
Off
4
Off
On
6
Off
Off
04
On
On
On
Off
On
On
05
On
On
On
Off
On
Off
06
On
On
On
Off
Off
On
07
On
On
On
Off
Off
Off
See note below
Note:
PLCĆ5/11 can scan rack 03.
PLCĆ5/20, PLCĆ5/30, PLCĆ5/40, PLCĆ5/60 can scan racks 01Ć07.