2–14

Installing Your Module

Publication 1771-UM001A-US-P - February 2000

If this is the last remote I/O adapter on the link, you must use a
terminating resistor to terminate both ends of the remote I/O link
(scanner end and last adapter end). Connect the terminator across
terminals 1 (blue) and 3 (clear).

The size of the terminator is determined by the system configuration.
Older configurations use a 150 ohm resistor at both ends. With newer
products that can support it, you can use an 82 ohm terminator at
both ends. The 82 ohm terminators provide “extended node”
capability which allows you to have up to 32 physical devices on the
RIO link. (The number of logical racks capable of being addressed
by the scanner is not affected.) This allows 1/4, 1/2 and 3/4 racks,
Dataliners, Redipanels and Panelview devices to be attached to the
link.

!

ATTENTION: Devices that are operating at 230.4K
Baud must have 82 ohm terminators in place for proper
operation.

Certain products are not compatible with the extended node
capabilities obtained with the use of the 82 ohm terminator resistors.
These products are listed below.

Table 2.E

NonĆcompatible Products

Device

Series

Scanners Ć

1771ĆSN

All

1771ĆSD

All

1772ĆSD2

All

1775ĆSR

All

1775ĆS4A

All

1775ĆS4B

All

Adapters Ć

1771ĆAS

All

1771ĆASB

Series A

1771ĆDCM

All

Miscellaneous Ć 1771ĆAF

All

1771ĆAF1

All

Installing the Terminator

Compatibility of 1771

Remote I/O Productswith

Extended Node Numbers