Rockwell Automation 1771-ASB/E Remote I/O Adapter User Manual User Manual
Page 27

2–13
Installing Your Module
Publication 1771-UM001A-US-P - February 2000
Figure 2.14
Field Wiring Arm Connection Diagram for the 1771ĆASB Series E
1 Line 1
2 Shield
3 Line 2
4 No connection
5 No connection
6 No connection
7 No connection
8 No connection
9 No connection
10 No connection
11 In
12 Ret
Reset
User supplied
I/O rack restart
pushbutton
AllenĆBradley Cable (cat. no. 1770ĆCD)
Blue
Shield
Clear
1
2
3
4
5
6
7
8
9
10
11
12
Cable
17343
ATTENTION: Do not make connections to
terminals 4 through 10. These terminals
are connected internally (1 to 4, 2 to 5 and
3 to 6) and cannot be used for any other
purpose.
Remote I/O Cable
!
ATTENTION: Do not remove or insert the adapter
module from the I/O chassis while system power is on.
Otherwise, you may damage module circuitry.
Terminals 1 and 4, 2 and 5, and 3 and 6 are internally connected on
the module. If you use these terminals (4, 5, and 6) for connection of
additional adapter modules, you disconnect the remaining adapter
modules in the series connection when you disconnect the remote
I/O adapter module wiring arm. If this is unsuitable for your
application, make your connections to terminals 1, 2, and 3 only.