2–13

Installing Your Module

Publication 1771-UM001A-US-P - February 2000

Figure 2.14

Field Wiring Arm Connection Diagram for the 1771ĆASB Series E

1 Line 1
2 Shield

3 Line 2

4 No connection

5 No connection
6 No connection

7 No connection
8 No connection

9 No connection

10 No connection
11 In

12 Ret

Reset

User supplied

I/O rack restart

pushbutton

AllenĆBradley Cable (cat. no. 1770ĆCD)

Blue

Shield

Clear

1

2

3

4

5

6

7

8

9

10

11

12

Cable

17343

ATTENTION: Do not make connections to

terminals 4 through 10. These terminals

are connected internally (1 to 4, 2 to 5 and

3 to 6) and cannot be used for any other

purpose.

Remote I/O Cable

!

ATTENTION: Do not remove or insert the adapter
module from the I/O chassis while system power is on.
Otherwise, you may damage module circuitry.

Terminals 1 and 4, 2 and 5, and 3 and 6 are internally connected on
the module. If you use these terminals (4, 5, and 6) for connection of
additional adapter modules, you disconnect the remaining adapter
modules in the series connection when you disconnect the remote
I/O adapter module wiring arm. If this is unsuitable for your
application, make your connections to terminals 1, 2, and 3 only.