Addressing Modes for Your Remote I/O

Publication 1771-UM001A-US-P - February 2000

Thirty-two-point I/O modules need 32 input or 32 output bits in the
processor’s image table. Because only 16 input and 16 output bits
are available for each I/O group, to address a 32-point I/O module,
the remote I/O adapter module uses the unused input or output word
associated with the adjacent I/O slot.

Refer to Figure 3.12. When the 1771-ASB remote adapter module
addresses a 1-slot I/O group containing a 32-point I/O module, the
adapter module uses the unused word assigned to the adjacent I/O
module slot. For example, the adapter module uses the unused input
word associated with I/O slot 1 (because that slot must hold an
output module and does not use its input word).

Figure 3.13 illustrates the concept of 1-slot addressing with two
32-point I/O modules.

Figure 3.12

1Ćslot I/O Group Concept With 32Ćpoint I/O Modules

32-point I/O M odules

Input W ord 0

O utput W ord 0

Image Table

W ords Allocated

for I/O G roup 0

Input W ord 1

O utput W ord 1

Image Table

W ords Allocated

for I/O G roup 1

Slot 0

Input M odule

I/O G roup 0

Slot 1

O utput M odule

I/O G roup 1

14258