Settings for 1771–AS and 1771–ASB Series A, B, C and D Remote I/O Adapters

B–11

Publication 1771ĆUM001A-US-P - February 2000

Figure B.11

Module Switch Assembly Settings for 1771-ASB series C

and D Adapters for PLCĆ5 Family Processors With

Complementary I/O

1 2 3 4 5 6 7 8

O

N
O

F

F

First I/O group number

(Table B.H)

I/O rack number

(Table B.H)

Address Switch Assembly

(S1)

Switch Assembly

(S2)

Pressed in at top

Closed (ON)

Pressed in at bottom

Open (OFF)

Always ON

ON Ć Primary chassis

OFF Ć Complementary chassis

ON Ć Primary chassis

OFF Ć Complementary chassis

O

N
O

F

F

1 2 3 4

5 6

Link Response Ć on for series B emulation

Scan Ć on for all but last 4 slots

off for all slots

off for unrestricted

10801ĆI

Switch Position

1

2

ON OFF 57.6K Baud Ć 10,000ft

OFF OFF 115.2K Baud Ć 5,000ft

ON ON

Not Used

Maximum I/O

chassis distance(see note)

OFF ON

230.4K Baud Ć 2,500ft

Note: PLCĆ5/15 and 5/25 processors

operate at 57.6K baud only.

Off

Table B.H

I/O Rack Selection for PLCĆ5 Family Processors with

Complementary I/O

I/O

Rack #

Switch

1

2

3

4

5

6

1st I/O Group

Number

Switch Selections

7

8

01

On

On

On

On

On

Off

0

On

On

02

On

On

On

On

Off

On

2

On

Off

03

On

On

On

On

Off

Off

4

Off

On

6

Off

Off

04

On

On

On

Off

On

On

05

On

On

On

Off

On

Off

06

On

On

On

Off

Off

On

07

On

On

On

Off

Off

Off

See note below

Note:

PLCĆ5/11 can scan rack 03.

PLCĆ5/20, PLCĆ5/30, PLCĆ5/40, PLCĆ5/60 can scan racks 01Ć07.