I/o chassis/adapter module combinations, Summary, I/o chassis/adapter module combinations summary – Rockwell Automation 1771-ASB/E Remote I/O Adapter User Manual User Manual

Page 55

Advertising
background image

3–25

Addressing Modes for Your Remote I/O

Publication 1771-UM001A-US-P - February 2000

Table 3.C shows the addressing methods you can achieve with the
Series B chassis and the various remote I/O adapter modules.

Table 3.C

Series B Chassis/Adapter Module Combinations

Remote I/O Adapter Module

Catalog Number

I/O Points

Per Module

Addressing Mode

2ĆSlot

1ĆSlot

1/2ĆSlot

1771ĆAS

8

Yes

No

No

16

*

No

No

32

No

No

No

1771ĆASB

Series A

8

Yes

Yes

No

Series A

16

*

Yes

No

32

No

No

No

1771ĆASB

Series B C D and E

8

Yes

Yes

Yes

Series B, C, D and E

16

*

Yes

Yes

32

No

*

Yes

* Conditional module placement: you must use an input module and an output

module in two adjacent slots of the I/O chassis beginning with slot 0.

IMPORTANT: Series A I/O chassis let you use 2Ćslot addressing with 8Ćpoint

I/O modules only, regardless of the type of adapter module you use. This chart

is valid for series B I/O chassis. You need series B I/O chassis to achieve 1Ćslot

and 1/2Ćslot addressing with 16Ćpoint and 32Ćpoint I/O modules.

In this chapter we discussed how to address your hardware and the
various remote I/O configurations and options you can use in your
remote system.

I/O Chassis/Adapter

Module Combinations

Summary