2–5

Installing Your Module

Publication 1771-UM001A-US-P - February 2000

Figure 2.4

Module Switch Assembly Settings for PLCĆ2 Family

Processors

1 2 3 4 5 6 7 8

1 2 3 4

First I/O group number

(Table 2.A)

I/O rack number

(Table 2.A)

Address Switch Assembly

(S1)

Switch Assembly

(S2)

SD Ć always OFF

SD2 Ć without complementary I/O Ć always OFF

SD2 Ć with complementary I/O Ć

ON Ć Primary chassis

OFF Ć Complementary chassis

Pressed in at top

(ON)

Pressed in at bottom

(OFF)

Maximum I/O

chassis distance

SD Ć always ON

SD2 Ć without complementary I/O

Ć always ON

SD2 Ć with complementary I/O Ć

ON Ć Primary chassis

OFF Ć Complementary chassis

Always ON

5 6

Link Response Ć ON for series B emulation

Scan Ć ON for all but last 4 slots

OFF for all slots

OFF for unrestricted

Switch Position

1

2

57.6K Baud Ć 10,000ft

115.2K Baud Ć 5,000ft

Not Used

Not Used

10798ĆI

ATTENTION: Link response switch must

be ON when using the following scanner

modules:

1772ĆSD2

ON

OFF

OFF

OFF

ON

ON

ON

OFF

Off

(ON)

(OFF)

(ON)

(OFF)

OPEN

OPEN

Table 2.A

I/O Rack Number and First I/O Group Switch Selections for

the Address Switch Assembly S1 (PLCĆ2 Family

Processors)

I/O Rack

Number

Switch Selections

4

5

6

First I/O Group

Number

Switch Selections

7

8

1

On

On

On

0

On

On

2

On

On

Off

2

On

Off

3

On

Off

On

4

Off

On

4

On

Off

Off

6

Off

Off

5

Off

On

On

6

Off

On

Off

7

Off

Off

On

Advertising