2–9

Installing Your Module

Publication 1771-UM001A-US-P - February 2000

After setting the adapter module switch assemblies, you must also

set the I/O chassis backplane switches

Setting the Backplane Switch Assembly

The backplane switch assembly is located on the backplane of the
I/O chassis. You use it to select:

the last state of all outputs

the processor restart lockout feature

1/2-, 1- or 2-slot addressing

the last chassis in the I/O system (for PLC-2 family processors)

Refer to the table below for backplane switch setting illustrations for
the various processors.

For Processor:

Refer to:

PLCĆ2

Figure 2.8, page 2-9

PLCĆ3

Figure 2.9, page 2-10

PLCĆ5

Figure 2.10, page 2-10

PLCĆ5 remote configuration

Figure 2.11, page 2-11

PLCĆ5/250

Figure 2.12, page 2-11

Figure 2.8

I/O Chassis Backplane Switch Assembly Settings for

Remote Adapter Module in PLCĆ2 Family Processor System

Processor Restart Lockout Ć

When ON, processor can restart I/O chassis

When OFF, I/O chassis must be restarted at the chassis.

Addressing Switch Ć

ON Ć 1Ćslot addressingselected

OFF Ć 2Ćslot addressingselected

Last State Switch Ć

When ON, outputs of this chassis remain

in last state.

When OFF, outputs of this I/O chassis are

deenergized when a fault is detected.

Always OFF

Last Chassis Switch Ć

ON Ć Chassis does not contain the highest numbered I/O

group for the associated rack number

OFF Ć Chassis does contain the highest numbered I/O

group for the associated rack number

If you have only a primary chassis, set this

switch to OFF.

If you have both primary and complementary

chassis, set the primary chassis to ON and the

complementary chassis to OFF.

1080

ATTENTION: Set switch 1 to the OFF position

to deenergize outputs wired to this chassis when a

fault is detected. If switch 1 is set to the ON

position, outputs connected to this chassis remain

in their last state when a fault occurs and machine

motion may continue after fault detection.

O

O

12

3
456

7
8

N

F

F

Always OFF

Setting the I/O Chassis

Switches