Rockwell Automation 1771-ASB/E Remote I/O Adapter User Manual User Manual

Page 36

Advertising
background image

3–6

Addressing Modes for Your Remote I/O

Publication 1771-UM001A-US-P - February 2000

Figure 3.5

16Ćpoint Input and Output Modules Using Two Words of the

Image Table

17 16 15 14

12

10 07 06 05

03 02 01 00

04

11

13

O utput im age table word corresponding

to the I/O group.

17 16 15 14

12

10 07 06 05

03 02 01 00

04

11

13

Input im age table word corresponding

to the I/O group.

00

01

02

03

04

05

06

07

10

11

12

13

14

15

16

17

00

01

02

03

04

05

06

07

10

11

12

13

14

15

16

17

Input

Term inals

O utput

Term inals

15559

2Ćslot I/O Group

Because these modules use a full word in the image table, the only
type of module you can use in a 2-slot I/O group with a 16-point
module is one that performs the opposite (complementary) function;
an input module complements an output module and vice-versa.

You can use an 8-point module with a 16-point module in a 2-slot
group; it must perform the opposite function. However, eight bits in
the I/O image table are unused.