Settings for 1771–AS and 1771–ASB Series A, B, C and D Remote I/O Adapters

B–7

Publication 1771ĆUM001A-US-P - February 2000

Figure B.7

Module Switch Assembly Settings for 1771-ASB series C

and D Adapters for PLCĆ3 Family Processors

1 2 3 4 5 6 7 8

O

N
O

F

F

First I/O group number

(Table B.D)

I/O rack number

(Table B.D)

Address Switch Assembly

(S1)

Switch Assembly (S2)

Pressed in at top

Closed (ON)

Pressed in at bottom

Open (OFF)

O

N
O

F

F

1 2 3 4

5 6

Switch Position

1

2

57.6K Baud Ć 10,000ft

115.2K Baud Ć 5,000ft

Not Used

Maximum I/O

chassis distance

Link Response Ć ON for series B emulation

Scan Ć On for all but last 4 slots

Off for all slots

OFF for unrestricted

Always OFF

10799ĆI

ATTENTION: Link response switch must

be ON when using the following scanner modĆ

ules:

1775ĆS4A

1775ĆS4B

1775ĆS5

1775ĆSR5

1775ĆSR

ON

OFF

OFF

OFF

ON

ON

ON

230.4K Baud Ć 2,500ft

1

OFF

1 230.4K Baud with 1775ĆS5 revision A/G, and

1775ĆSR5 revision A/G scanners only.

Off

Table B.D

I/O Rack Switch Selections for the Address Switch

Assembly (PLCĆ3 Family Processors)

Rack

#

Switch Setting

1

2

3

4

5

6

Rack

#

Switch Setting

1

2

3

4

5

6

Rack

#

Switch Setting

1

2

3

4

5

6

Rack

#

Switch Setting

1

2

3

4

5

6

00

On On On On On On

20

On Off On On On On

40

Off On On On On On

60

Off Off On On On On

01

On On On On On Off

21

On Off On On On Off

41

Off On On On On Off

61

Off Off On On On Off

02

On On On On Off On

22

On Off On On Off On

42

Off On On On Off On

62

Off Off On On Off On

03

On On On On Off Off

23

On Off On On Off Off

43

Off On On On Off Off

63

Off Off On On Off Off

04

On On On Off On On

24

On Off On Off On On

44

Of On On Off On On

64

Off Off On Off On On

05

On On On Off On Off

25

On Off On Off On Off

45

Off On On Off On Off

65

Off Off On Off On Off

06

On On On Off Off On

26

On Off On Off Off On

46

Off On On Off Off On

66

Off Off On Off Off On

07

On On On Off Off Off

27

On Off On Off Off Off

47

Off On On Off Off Off

67

Off Off On Off Off Off

10

On On Off On On On

30

On Off Off On On On

50

Off On Off On On On

70

Off Off Off On On On

11

On On Off On On Off

31

On Off Off On On Off

51

Off On Off On On Off

71

Off Off Off On On Off

12

On On Off On Off On

32

On Off Off On Off On

52

Off On Off On Off On

72

Off Off Off On Off On

13

On On Off On Off Off

33

On Off Off On Off Off

53

Off On Off On Off Off

73

Off Off Off On Off Off

14

On On Off Off On On

34

On Off Off Off On On

54

Off On Off Off On On

74

Off Off Off Off On On

15

On On Off Off On Off

35

On Off Off Off On Off

55

Off On Off Off On Off

75

Off Off Off Off On Off

16

On On Off Off Off On

36

On Off Off Off Off On

56

Off On Off Off Off On

76

Off Off Off Off Off On

17

On On Off Off Off Off

37

On Off Off Off Off Off

57

Off On Off Off Off Off

77

Not valid

1st I/O Group

Number

Switch Selections

7

8

Note:

Rack address 77 is an illegal configuration.

PLCĆ3 processors can scan racks 0Ć76.

0

On

On

2

On

Off

4

Off

On

6

Off

Off