Settings for 1771–AS and 1771–ASB Series A, B, C and D Remote I/O Adapters

B–12

Publication 1771ĆUM001A-US-P - February 2000

Figure B.12

I/O Chassis Backplane Switch Assembly Settings for

1771-AS Remote Adapter Module in PLC-2 Family

Processor System

1 2 3 4 5 6 7 8

O

N
O

F

F

Processor Restart Lockout -

When ON, processor can restart I/O chassis

When OFF, I/O chassis must be restarted at

the chassis.

AddressingSwitch -

ON - 1-slot addressingselected

OFF - 2-slot addressingselected

Last State Switch -

When ON, outputs of this chassis

remain in last state.

When OFF, outputs of this I/O

chassis are deenergized when a

fault is detected.

Always OFF

Last Chassis Switch -

ON - Chassis does not contain the highest numĆ

bered I/O group for the associated rack number

OFF - Chassis does contain the highest numbered

I/O group for the associated rack number

If you have only a primary chassis, set this

switch to OFF.

If you have both primary and complementary

chassis, set the primary chassis to ON and the

complementary chassis to OFF.

Caution: Set switch 1 to the OFF position

to deenergize outputs wired to this chassis

when a fault is detected. If switch 1 is set to

the ON position, outputs connected to this

chassis remain in their last state when a fault

occurs and machine motion may continue

after fault detection.

10823-I

Figure B.13

I/O Chassis Backplane Switch Assembly Settings for

1771-AS Remote Adapter Module in PLC-3 Family

Processor System

1 2 3 4 5 6 7 8

O

N
O

F

F

Processor Restart Lockout -

When ON, processor can restart I/O chassis

When OFF, I/O chassis must be restarted at

the chassis.

Last State Switch -

When ON, outputs of this chassis

remain in last state.

When OFF, outputs of this I/O chassis

are deenergized when a fault is

detected.

Always OFF

Caution: Set switch 1 to the OFF position

to deenergize outputs wired to this chassis

when a fault is detected. If switch 1 is set to

the ON position, outputs connected to this

chassis remain in their last state when a fault

occurs and machine motion may continue

after fault detection.

1771-A1/A1B chassis in PLC-3 Backup

ON - If any 1771-A1/A1B chassis conĆ

tains startingI/O group 0 with 2-slot

addressingand the PLC-3 is configured

in backup mode.

OFF - All other times.

10824-I