Rockwell Automation 1771-ASB/E Remote I/O Adapter User Manual User Manual

Page 42

Advertising
background image

3–12

Addressing Modes for Your Remote I/O

Publication 1771-UM001A-US-P - February 2000

When using double-slot block-transfer modules:

The left slot of the complementary I/O group must be empty.

You can only place an 8-point output module (if any) in the
right slot of the complementary I/O group.

When using single-slot block-transfer modules:

The right slot of the primary I/O group can be another
single-slot block-transfer module, or an 8-point input or output
module.

The left slot of the complementary I/O group must be empty.

You can place an 8-point output module in the right slot of the
complementary I/O group; this slot must be empty if the
corresponding slot in the primary I/O group is a single-slot
block-transfer module.

When you select 2-slot addressing, each pair of slots (one I/O group)
is assigned to the corresponding pair of words in the input and
output image tables. You assign one I/O rack number to eight I/O
groups (Figure 3.10).

Figure 3.10

I/O Image Table and Corresponding Hardware for One

Assigned Rack Number with 2Ćslot Addressing