Acceptable chassis combinations – Rockwell Automation 1771-ASB/E Remote I/O Adapter User Manual User Manual
Page 54
![background image](/manuals/579882/54/background.png)
3–24
Addressing Modes for Your Remote I/O
Publication 1771-UM001A-US-P - February 2000
Not all chassis combinations are acceptable in making I/O rack
number assignments. For example, a 1771-A4B I/O chassis cannot
complete an assigned I/O rack number that starts in a 1771-A1 I/O
chassis. Refer to Figure 3.B for acceptable beginning I/O group
numbers when making your I/O rack number assignments.
Table 3.B
Acceptable Beginning I/O Group Numbers
If you select:
and:
The beginning I/O group number
can be:
2Ćslot addressing
4Ćslot chassis
0, 2, 4, 6
8Ćslot chassis
0, 2, 4
12Ćslot chassis
0, 2
16Ćslot chassis
0
1Ćslot addressing
4Ćslot chassis
0, 2, 4, 6
8Ćslot chassis
0, 2, 4, 6
12Ćslot chassis
0, 2, 4,
16Ćslot chassis
0
1/2Ćslot addressing
4Ćslot chassis
0
8Ćslot chassis
0
12Ćslot chassis
0
16Ćslot chassis
0
Acceptable Chassis
Combinations