Q. How do I add a 1771-ASB adapter module to my SLC

1747-SN scanner remote I/O network?

A. Enter the correct rack number, rack size and starting group in

the SLC500 program I/O configuration G-file data screen.
With the correct communication rate set on the scanner,
download the program to the SLC processor and switch to
Run mode. Communication to the adapter will commence.

Q. Ever since I installed fiber optics on my remote I/O network,

the adapters won’t communicate.

A. This is probably an installation issue. Check your installation

for the correct application, connection and termination of
fiber optic cable, and the correct setup of the fiber optic
module (1771-AF, -AF1). Make sure that no length of blue
hose on this network is less than 10ft long, including the
blue hose connections from the processor, scanner or adapter
to the fiber optic module in the same chassis.

Q. I have a 12-slot chassis but only the modules in the first 8

slots are recognized by my program.

A. Check the scan switch (switch S2, position 4) for correct

setting. It probably is set ON “scan all but the last 4 slots.”
Set it to OFF.

Q. I just installed a 1771-IL series B analog input module in my

remote I/O chassis which already has a 1771-ASB series A
adapter. Now my block transfers to this module are erroring.

A. Adapter modules prior to series C, firmware revision D, are

not compatible with the following modules:
1771-CFM, -CFMK Series A

1771-DB Series B

1771-DMC Series A

1771-DMC1 Series A

1771-DMC4 Series A

1771-DXS2 Series A

1771-DXS4 Series A

1771-HS1, -HS3A, -HS3CR

1771-IFE Series C

1771-IFM Series A andB

1771-IL, -ILK Series B

1771-IR, -IRK Series B

1771-IXE, -IXEK Series B

1771-IXHR Series B

1771-NXXX Series A

1771-OEM1 Series A

1771-QB Series B