Standard Drive Parameters
Appendix A
[Pr - 5.09]
Disabled Braking Speed
Ultraware Name
Stopping Functions: Braking Application Speed
Description
The Disabled Braking Speed is the feedback speed below
which the motor break is engaged, after disabling the
drive.
Range
0…1000
Default
100
Units
Rotary motors: rpm; Linear motors: mm/s
When Enabled
All
Applicable Operating Mode
Servo-Off -> Setting
Modbus Address
[Pr - 5.10]
Following Error Limit
Ultraware Name
Following Error Limit
Description
A following error fault occurs when the difference
between position command and actual position is greater
than this parameter.
Range
0…2,147,483,647
Default
99,999
Units
Counts
When Enabled
Immediately
Applicable Operating Mode
Follower
Modbus Address
Pr5-10[Lo] = 510, Pr5-10[Hi] = 511
[Pr - 5.11]
Reserved
When Enabled
Reserved for future use.
[Pr - 5.12]
AC line loss fault delay
Ultraware Name
AC Line Loss Fault Delay
Description
The AC Line Loss Fault is inhibited for this amount of time,
when a loss of AC power is detected.
Range
20…1000
Default
20
Units
ms
When Enabled
Servo-Off -> Setting
Applicable Operating Mode
All
Modbus Address