Preliminary review, Troubleshooting flow charts, Preliminary review troubleshooting flow charts – Rockwell Automation 8720MC 8720MC Regenerative Power Supply User Manual User Manual

Page 114: 8720mc-rps regenerative power supply does not run

Advertising
background image

1.

Turn OFF the input power to the 8720MC-RPS Regenerative
Power Supply and wait until "POWER" lamp goes OFF.

2.

Verify that the DC bus voltage is zero and the DC bus
capacitors are completely discharged.

3.

Check the following:

Check that no terminal is loose and that termination to the
connectors is correct.

Check that the incoming power voltage is correct.

Check that the unit was installed correctly.

Verify that all the coils possibly generating electrical noise
around the unit, such as relays, solenoid-valves, and
magnetic brakes are provided with surge suppressors.

8720MC-RPS Regenerative Power Supply Does Not Run

9-2

Inspecting Trouble and Recovering

Preliminary Review

Troubleshooting Flow
Charts

The unit does not run.

Power supply ON?

YES

YES

YES

YES

Check the following:

Circuit breaker

Protection fuse

Wiring

Power supply

Check wiring for the sequence
signals.

Check the following:

Setting of Precharge/Discharge

Time (F.014)

Precharge/Discharge Resistor,

and wiring to it

Check the following:

Wiring for sequence signals

Wiring to coil of main magnetic

contactor

Order of phases of wiring for main

power supply and control power

NO

NO

NO

NO

RUN sequence

input entered?

Precharge is

completed?

Main

magnetic contactor

operate?

The unit is defective.

Replace the unit.