Start and adjustment 5-5 rst prg ent, Rst prg ent – Rockwell Automation 8720MC 8720MC Regenerative Power Supply User Manual User Manual

Page 81

Advertising
background image

Step 2.4

Press the

key.

The display indicates the second
Factory parameter.

Step 2.5

Press the ENT key.

The display shows that 37 KW
(65 Amps.) unit for 460 V is
selected. If the display does not
match the actual unit rating,
first set the password (F.000),
and then set again the Unit
Selection conforming to the unit
rating (refer to the section
"Factory Parameters" in Chapter
7).

Step 2.6

Press the PRG key.

The display indicates the second
Factory parameter (F.001).

Step 2.7

Press the PRG key.

The display shows "F.---"
indicating that you can access
the Factory parameters.

Step 2.8

Press the PRG key.

The operation panel returns to
monitor mode again. The
display indicates the input
current and the "A" status LED
turns ON. This display shows
the input current is 0 Amp.