4-4

Wiring

Figure 4.1
Typical Connection of AC Input Power Wiring for Single Unit of
Model 8720MC-RPS027 and 8720MC-RPS065

ATTENTION:

Special caution must be paid to wiring

to the 8720MC-RPS Regenerative Power Supply when
connecting multiple units in parallel. The phases of AC
input power to the main power supply terminals (L

1

, L

2

and L

3

) and to the control power terminals (L

1AUX

,

L

2AUX

, and L

3AUX

) and the polarity of DC bus output (P

and N) of all the connected units must be the same.
Failure to observe this precaution could result in
destruction of the equipment, severe bodily injury or
loss of life.

!

MC

L

1

P

L

1AUX

L

2AUX

L

3AUX

PR1

PR2

PR3

MC1

MC2

PWR

MC

24V

8720MC-RPS

Regenerative

Power Supply

Unit

MC

Circuit

Breaker <4

(CB)

Line Filter <5

for AC Input

Power

Single-phase

Line Filter <5

Main

Magnetic

Contactor

(MC)

Reactor <11

Harmonic

Filter

Terminal Block for

Control Power (TB2)

100 to 115 VAC

or

200 to 230 VAC

380 to

460 VAC

RUN On/Off

Terminal Block for
Sequence Signals (TB3)

Terminal Block for Main
Power Supply (TB1)

Protection Fuse <2

Terminals P and N <6
of Load Equipment

1>

The phases of the AC input power to the main supply terminals L

1

, L

2

and L

3

must be same as those of the control power

to the control power terminals L

1AUX

, L

2AUX

and L

3AUX

.

2>

It is recommended to install the DC bus protection fuses on the both lines to the terminals P and N to prevent ground fault,

when more than one drive is connected to the 8720MC-RPS Regenerative Power Supply.

3> Turn ON the switch SW7-1 on the Regulator Board without fail.
4> Both a three-phase circuit breaker and fuses are not required. Check your local code to determine if fuses should be

used instead of a circuit breaker.

5> When the 8720MC-RPS Regenerative Power Supply must conform with the requirements of CE Mark, install a line filter in

the AC input power line and a single-phase line filter in the power supply line to the main magnetic contactor.

6> The length of the DC bus wiring runs should not exceed 2 meters. It is also recommended to use twisted shielded cable.
7> The length of the wiring in the cabinet must be as short as possible.
8> The length of the wiring from the E terminal of the Harmonic Filter to the Grounding Terminal must be as short as possible.
9>

The physical location of the Harmonic Filter and Varistor relative to the Contactor and Line Reactor is important.
Connect these devices in the relative positions shown in this illustration.

10>

Because driving current of sequence input signals is 5mA and below, use a contact of which minimum applicable load is 5mA and below.

11>

Use the reactor in maximum surrounding air temperature of 55 degree C (131 degree F) and below.