Default Settings of All Parameters

User's Setting

Setting

Date

Default Value

750 V

150%

150%

0

28 Amps
65 Amps
130 Amps
190 Amps
195 Amps
380 Amps
570 Amps

027.b: 28 Amps
065.b: 65 Amps
130.b: 130 Amps
190.b: 190 Amps
195.b: 195 Amps
380.b: 380 Amps
570.b: 570 Amps

1.00 times

64 rad/sec

5.00 times

128 rad/sec

800 V

400V

550 V

10 kHz: For Model
8720MC-RPS027 and
8720MC-RPS065
5 kHz: For Model
8720MC-RPS190

6.0 microseconds

0.50 seconds

See the previous
section.

3.0 seconds

(3)

See the previous
section.

1.000

On

On

Setting Range

275 to 750 V

0 to 150%

0 to 150%

0 to 999

027.b
065.b
130.b
190.b
195.b
380.b
570.b

027.b: 10 to 35Amps
065.b: 10 to 70 Amps
130.b: 20 to 140 Amps
190.b: 30 to 210 Amps
195.b: 30 to 215 Amps
380.b: 60 to 430 Amps
570.b: 90 to 645 Amps

0.01 to 10.0 times

1 to 3,000 rad/sec

0.01 to 30.00 times

1 to 3,000 rad/sec

325 to 900 V

200 to 600 V

200 to 550 V

5, 10 and 15 kHz

1.5 to 15.0 microseconds

0.05 to 3.00 seconds

100 to 8,000 micro-henry

0.5 to 15.0 seconds

50 to 2,000 W

0.900 to 1.100

OFF, On

OFF, On

Parameter Name

DC Bus Voltage Reference

FWD Current Limit

REV Current Limit

Password

Unit Selection

Rated Current

Current Control Proportional Gain

Current Control Integral Gain

Voltage Control Proportional Gain

Voltage Control Integral Gain

Bus Overvoltage Detection Level

Bus Low Voltage Detection Level

AC Overvoltage Detection Level

Carrier Frequency

Deadtime

Allowable Time for Instantaneous
Power Loss

AC Reactor Capacity

Precharge/Discharge Time

Wattage of Precharge/Discharge
Resistor

DC Bus Voltage Offset

(1)

Discharge Function Enable

(1)

Version Information

Selecting of Wiring Error (LE)
Detecting Function

(2)

Parameter
Number

User
Parameters

Factory
Parameters

U.000

U.001

U.002

F.000

F.001

F.002

F.003

F.004

F.005

F.006

F.007

F.008

F.009

F.010

F.011

F.012

F.013

F.014

F.015

F.016

F.017

F.018

F.019

B-2

Default Parameter Settings

(1)

These parameters are available from software version No. 2.00 or later only.

(2)

This parameter is available from software version No. 3.00 or later only.

(3)

This parameter must be set to 6.0 seconds for 8720MC-RPS190 unit.