Verify that there is no debris such as metal shavings around the
unit.

Check that there is adequate clearance around the unit.

Verifying the Rating of the 8720MC-RPS Regenerative Power
Supply

Before powering up the 8720MC-RPS Regenerative Power Supply,
check the following:

Check the unit's nameplate and confirm that the installed
8720MC-RPS Regenerative Power Supply has an enough rating
for the load.

Check that the incoming power is rated correctly for the rating

of the 8720MC-RPS Regenerative Power Supply.

Check that the disconnect (breaker) and the fuses provided for
the branch circuit protection are rated correctly.

Check that the AC reactor is rated correctly.

Verifying Wiring

Check the following before powering up the 8720MC-RPS
Regenerative Power Supply:

Verify that the 8720MC-RPS Regenerative Power Supply was
installed rigidly.

Check that there is no miswiring.

Check that no terminals or connection are loose.

Verify that there are no short circuits with regard to the
terminals L

1

, L

2

, L

3

, P, N and G. Also verify that there are no

ground faults with regard to these terminals except terminal G.

Check that the terminals L

1AUX

, L

2AUX

and L

3AUX

are not

shorted.

Verify that the electronic size is within the specification range
and the wire is tightened correctly.

Verify that the operations of the sequence control signals are
normal.

Use the following procedure to turn power to the 8720MC-RPS
Regenerative Power Supply ON:

Step 1.

Turn the RUN sequence signal OFF.

Step 2.

Turn the input power breaker to the ON position.

Step 3.

Apply power to the 8720MC-RPS Regenerative Power
Supply.

5-2

Start and Adjustment

Powering up the 8720MC-RPS
Regenerative Power Supply