Verify the following when installing sequence signal wiring:

Twisted pair wires of 0.2 to 0.5 mm

2

should be used for the

signal line.

Verify that the sequence signal wiring is separated from the
power wiring (main power supply wiring, control power wiring
and DC bus power wiring). Malfunction of the 8720MC-RPS
Regenerative Power Supply is possible if the control wires
are separated from the AC and DC power wires.

Use a separate duct for the sequence signal wiring. It is
recommended to use a dedicated duct for the sequence signal
wiring.

Do not route the sequence signal wiring near any equipment
which is producing electromagnetic interference.

Figure 4.11 shows a typical connection of sequence control signals.

Figure 4.11
Typical Connection of Sequence Control Signals