Operating the 8720mc-rps regenerative power supply – Rockwell Automation 8720MC 8720MC Regenerative Power Supply User Manual User Manual
Page 79

Start and Adjustment
5-3
Step 4.
Verify that the unit powers up properly without incident
such as abnormal sound or nasty smell.
Step 5.
Verify that there is no input power voltage drop or short
circuit.
Step 6.
Verify that the rating of the 8720MC-RPS Regenerative
Power Supply matches the parameter setting of the Unit
Selection (F.001).
For Step 6, more information will be given in the section
"Operating the 8720MC-RPS Regenerative Power Supply" in this
Chapter.
This section describes the following basic start-up and operation
procedure:
•
Powering up
•
Precharging
•
Verifying the parameter of the Unit Selection
•
Checking the DC bus voltage
•
Changing the DC bus voltage reference value
•
Discharging
•
Disconnecting power
This start-up procedure describes how to set the minimum set of
parameters. Your application may require programming other
parameters in addition to those described in this start-up
procedure. Refer to Chapter 8 for description of all parameters to
verify whether you need to program any additional parameters as
well.
In this manual, you will see references to parameters names and the
numbers that identify them for the 8720MC-RPS Regenerative
Power Supply. This manual uses the same format that will be
shown on the display to refer to parameters:
U.nnn
F.nnn
where:
nnn is a number
U designates User parameters
F designates Factory parameters.
Operating the 8720MC-RPS
Regenerative Power Supply