4-25

Wiring

on the terminal block TB2. Terminal PR3 should be left open.
See Chapter 2, Figure 2.2 "Terminals Blocks on the Main Circuit".
The Precharge/Discharge Time (F.014) may require a larger value
to accommodate the increased precharge time. The Wattage of
Precharge/Discharge Resistor (F.015) should also be increased to
the external precharge resistor wattage.

External circuit case

In the case of the RPS190 if the total capacitance is above
165,000

µ

f but less than 495,000

µ

f an external precharge resistor

connected as shown in Figure 4.10 must be provided. Table 4.8
provides the minimum resistance value for the external precharge
resistor, 1.5 ohms in the case of the RPS190. The wattage [W] is
determined by the equation presented above.

Figure 4.10
Example of Wiring when Precharge/Discharge Circuit of the 8720MC-RPS190 is
configured with an External Circuit

CN2

CN2

CN4

1
2
3

CN4

CN1

MC1
MC2

+24V2

0V2

NC

+24V3

0V3

SENS-out

L1

PR3

PR2

PR1

PRX

MC

PRX

PWR MCX

L4

L5

L6

L2

L3

L1 (R)
L2 (S)

L3 (T)

P
N

G

DISR

DIS

PWR

MCX

Relay for controlling
DC 24V control

DIS

L

1AUX

(R1)

L

2AUX

(S1)

L

3AUX

(T1)

PR1
PR2
PR3

ACL Unit

24V3
0V3
SENS
24V2
0V2
MC1
MC2

MC

RST

PWR

0V

24V

COM

IP

RDY

FR
FR

RED

1 R1
2 S1

3 T1

WHT

BLU

BDSR-1

CN1

G

SS441B:
AC 460V
SS4265:
AC 230V

L4

L5

L6

L1
L2
L3

L4
L5

L6

L1

L2

L3

<1

8720MC-EF190-VB

EMC Filter Unit

8720MC-RPS190

YLW

BLK

RED

R

BL

Y

BR

BR

Circuit

Breaker

(CB)

A1
A2
A3
A4
A5
B1
B2
B3
B4
B5

A1
A2
A3
A4
A5
B1
B2
B3
B4
B5

A1
A2
A3
A4
A5
B1
B2
B3
B4
B5

A1
A2
A3
A4
A5
B1
B2
B3
B4
B5

R1

S1

T1

Fan 3

Fan 2

RED

BLK

YLW

YLW

RED

BLK

Short

Terminals on ACL Unit

Fan

DC Output
Fuse

ACL Unit

AC

Input
Fuse

MCX

PRX

DIS

+24V

MC

MC

Power for Sequence Circuit

DC
Contactor

1> Remove the jumper between PR2 and PR3.
2> Use a relay with contact of which minimum applicable load is 5 mA and below.
3> Refer to the figure at the lower left corner of this figure indicating the terminals on the ACL unit. When the fan

inside the ACL unit is connected with an external power supply, do not fail to connect with the power supply
designated by NEC Class 2 (Power supply limited to 100VA and below and 8A and below even in case of Error).
Avoid the high voltage portion and the high temperature portion of the ACL unit when wiring the fan inside the
ACL unit.

4> Use the ACL unit in maximum surrounding air temperature of 55 degree C (131 degree F) and below.

<4

<3

<3

<2

<4

Advertising