4-7

Wiring

When Model 8720MC-RPS027 or 8720MC-RPS065 is operated in
the Power Regeneration Mode only

Figure 4.4
Wiring Model 8720MC-RPS027 or 8720MC-RPS065 Unit
Used as a Converter for the Power Regeneration Mode Only

It is possible to select the 8720MC-RPS units depending on the
regenerative power when only regenerated power of the unit
integrating converter and inverter is used. In this case, however,
the following cautions must be observed. Figure 4.4 shows wiring
of the 8720MC-RPS027 or 8720MC-RPS065 unit used as a
converter for the power regeneration mode only.

8720MC-RPS027
and
8720MC-RPS065

Main

Magnetic

Contactor

(MC1)

MC1

100 to 115 VAC

or

200 to 230 VAC

L

1

L

2

L

3

P

N

G

L

1AUX

L

2AUX

L

3AUX

PR1

PR2

PR3
MC1

MC2

PWR

READY

MC

24V

Circuit

Breaker

(CB2)

Circuit

Breaker

(CB1)

L

1

L

2

L

3

MC1

RUN On/Off

U

V

W

P

N

G

To AC Motor

Reactor

Reactor

Inverter

(Load Equipment)

8720MC-RPS

Regenerative Power

Supply Unit

(Dedicated for Power

Regeneration Mode)

Harmonic

Filter

Varistor

Fuse

1> The phases of the AC input power to the main supply terminals L

1

, L

2

and L

3

must be same as those of the control power

to the control power terminals L

1AUX

, L

2AUX

and L

3AUX

.

2> It is recommended to install the DC bus protection fuses on the both lines to the terminals P and N to prevent ground fault,

when plural number of load equipment is connected to the 8720MC-RPS Regenerative Power Supply.

3> Turn ON the switch SW7-1 on the Regulator Board without fail.
4> Wiring to be taken into cabinet must be as short as possible.
5> This connection is only used with AC input drives.
6> The length of the wiring from the E terminal of the Harmonic Filter to the Grounding Terminal must be as short as possible.
7> The physical location of the Harmonic Filter and Varistor relative to the Contactor and Line Reactor is important.

Connect these devices in the relative positions shown in this illustration.

8> Because driving current of sequence input signals is 5mA and below, use a contact of which minimum applicable load is 5mA and below.
9> Use the reactor in maximum surrounding air temperature of 55 degree C (131 degree F) and below.

Protection Fuse <2

Single Phase

Line Filter

Line Filter for
AC Input Power

<1

<2

<7

<8

<9

<6

E

READY