Rockwell Automation 8720MC 8720MC Regenerative Power Supply User Manual User Manual

Page 24

Advertising
background image

2-12

About 8720MC-RPS Regenerative Power Supply

Terminal Name

Control Power Terminals

Terminals to Connect
Precharge/Discharge
Resistor

Control Terminals for
Main Magnetic Contactor

Symbol

L

1AUX,

L

2AUX,

L

3AUX

PR1,
PR2,
PR3

MC1,
MC2

Description

To connect three-phase AC input power to the
control circuit.
For 460 V unit: 380 to 460 VAC +10%, -15%,
50/60 Hz +/-5%

To connect precharge/discharge resistor.
When the built-in resistor is used:

Jumper between PR2 and PR3, and open
PR1.

When an external resistor is used:

Connect the resistor between PR1 and
PR2, and open PR3.

When the unit is connected for power
regeneration mode only:

Open all the terminals PR1, PR2 and
PR3.

To be used as the control terminals for the
main magnetic contactor (rated for 250 VAC/
1 Amp or 30 VDC/1 Amp).

Control Power Terminal Block (TB2) for Model 8720MC-RPS027
and 8720MC-RPS065

The table below describes the terminals on the control power
terminal block (TB2) for Model 8720MC-RPS027 and
8720MC-RPS065.

Main Power Terminal Block (TB1) for Model 8720MC-RPS027 and
8720MC-RPS065

The table below provides the information of the terminals on use of
the terminals on the main power terminal block (TB1) for Model
8720MC-RPS027 and 8720MC-RPS065.

Terminal Name

Main Power
Terminals

DC Bus Terminals

Grounding Terminal

Symbol

L

1

, L

2

, L

3

P, N

G

Description

To connect three-phase AC input power to
the main circuit.
For 460 V unit: 380 to 460 VAC +10%,
-15%, 50/60 Hz +/-5%

To connect the 8720MC-RPS Regenerative
Power Supply to load equipment.

To ground the 8720MC-RPS Regenerative
Power Supply.

Advertising