Main power terminal bar for model 8720mc-rps190 – Rockwell Automation 8720MC 8720MC Regenerative Power Supply User Manual User Manual

Page 25

Advertising
background image

Main Power Terminal Bar for Model 8720MC-RPS190

The table below describes the terminals on the main power terminal
bar for Model 8720MC-RPS190.

Terminal Name

Control Power
Terminal

Terminals to Connect
Precharge/Discharge
Resistor

AC Reactor Fan
Power Terminals

Terminals for Fan Fault
Signal

Power Terminals for
Main Magnetic
Contactor MC
and Optional Fan

Control Terminaks for
Main Magnetic
Contactor

Symbol

L

1AUX,

L

2AUX,

L

3AUX

PR1,
PR2,
PR3

+24V3
0V3

SENS

+24V2
0V2

MC1
MC2

Description

To connect three-phase AC input power to the
control circuit.
For 460 V unit: 380 to 460 VAC +10%, -15%,
50/60 Hz +/-5%

To connect precharge/discharge resistor.
When the built-in resistor is used:

Jumper between PR2 and PR3, and open
PR1.

When an external resistor is used:

Connect the resistor between PR1 and
PR2, and open PR3.

When the unit is connected for power
regeneration mode only:

Open all the terminals PR1, PR2 and
PR3.

To supply AC power to the fan for the AC reactor
unit through the EM4000 EMC filter unit.

To enter fault signal of the fan for the AC reactor
unit.

To supply power to the main magnetic contactor
and the fan for the cabinet fan through the
8720MC-EF190 EMC filter unit.

To be used as the control terminals for the main
magnetic contactor.

Terminal Name

Main Power
Terminals

DC Bus Terminals

Grounding Terminal

Symbol

L

1

, L

2

, L

3

P, N

G

Description

To connect three-phase AC input power to
the main circuit.
For 460 V unit: 380 to 460 VAC +10%,
-15%, 50/60 Hz +/-5%

To connect the 8720MC-RPS Regenerative
Power Supply to load equipment.

To ground the 8720MC-RPS Regenerative
Power Supply.

T
B
2

T
B
4

Control Power Terminal Block (TB2) and Control Terminal Block
(TB4) for Model 8720MC-RPS190

The table below describes the terminals on the control power
terminal block (TB2) and the terminals on the control terminal
block (TB4) for Model 8720MC-RPS190.

2-13

About 8720MC-RPS Regenerative Power Supply

Advertising