4-2

Wiring

Name of Terminal

Main Terminals (Input)

DC Bus Terminals (Output)

Grounding Terminal (Earth)

Symbol

L

1

, L

2

, L

3

P, N

G

Size of Wire AWG/mm

2

#10 / 5.5 mm

2

#10 / 5.5 mm

2

#10 / 5.5 mm

2

Screw Size

M5

M5

M5

Name of Terminal

Main Terminals (Input)

DC Bus Terminals (Output)

Grounding Terminal (Earth)

Symbol

L

1

, L

2

, L

3

P, N

G

Size of Wire AWG/mm

2

#4 / 22 mm

2

#4 / 22 mm

2

#5 / 22 mm

2

Screw Size

M6

M6

M6

Name of Terminal

Main Power Supply
Terminals

DC Bus Terminals

Grounding Terminal

Symbol

L

1

, L

2

, L

3

P, N

G

Size of Wire AWG/mm

2

Larger than 38
mm

2

- 2 in parallel

(AWG #2 - 2 in
parallel)

Larger than 100mm

2

(AWG #4/0)

Larger than 38mm

2

(AWG #2)

Screw Size

M10

M10

M8

Attached Lugs

(1)

JST, R38-10
(M10) (6 Pieces)

JST, R100-10
(M10) (2 Pieces)

JST, R38-8 (M10)
(1 Piece)

(1)

UL-listed wires must be lugged by attached lugs.

JST is Japan Solderless Terminal Co.

Table 4.3
Recommended Maximum Wire Sizes for Model 8720MC-RPS190 Unit

Table 4.2
Recommended Maximum Wire Sizes for Model 8720MC-RPS065 Unit

Recommended Wire Sizes for Power Wiring to the Main Power
Terminal Block (TB1) and the Main Power Terminal Bars

Table 4.1 to 4.3 show the recommended wire sizes for power wiring
to the main power terminal block (TB1) and the Main Power
Terminal Bars. Table 4.1 shows the wire sizes for Model 8720MC-
RPS027 unit, Table 4.2 shows the wire sizes for Model 8720MC-
RPS065 unit, and Table 4.3 shows the wire sizes for Model
8720MC-RPS190 unit. The wire sizes shown assume full utilization
of the rated capacity of the RPS unit.

Table 4.1
Recommended Maximum Wire Sizes for Model 8720MC-RPS027 Unit

Recommended Wire Sizes for Power Wiring to the Control Power
Terminal Block (TB2) and the Control Terminal Block (TB4)

Table 4.4 shows the recommended wire sizes for power wiring to
the control power terminal block (TB2) and the control terminal
block (TB4).

Table 4.4
Recommended Wire Sizes for Power Wiring to the Control Power Terminals
and the control terminal block (TB4)

Name of Terminal

Main Terminals (Input)

DC Bus Terminals (Output)

Grounding Terminal (Earth)

Symbol

L

1AUX

, L

2AUX

, L

3AUX

PR1, PR2, PR3

MC1, MC2

Size of Wire

3.5 mm

2

(AWG #12)

3.5 mm

2

(AWG #12)

2.0 mm

2

(AWG #14)

Advertising