Rockwell Automation GV3000/SE AC Drive Ver. 6.06 Hdwe Ref., Installation, and Troubleshooting Manual User Manual
Page 104

A-2
GV3000/SE AC Drive Hardware Reference, Version 6.06
Table A.2 – Environmental Condition
Condition
Specification
Operating Temperature (Ambient)
0
°
to
+
40
°
C
(
32
°
to
104
°
F
)
Storage Temperature (Ambient)
-40
°
to
+
65
°
C
(−
40
°
to
+
149
°
F
)
Humidity
5 to 95% (non-condensing)
Table A.3 – Terminal Strip Input Specifications
Signal Type
Terminal(s)
Specification
Speed Reference Input
12-15
10 V (@ 50K ohm input
impedance or 20 mA)
Digital Inputs (1 - 8)
16
+24 VDC Isolated Supply
17
Remote/Local (Default)
18
Ramp1/Ramp2 (Default)
19
Forward/Reverse (Default)
20
Function Loss
21
Run/Jog
22
Reset
23
Stop
24
Start
Table A.4 – Terminal Strip Output Specifications
Signal Type
Terminal(s)
Specification
Analog Output
10 -11
scaled signal
0-10 VDC or 4-20 mA
Snubber Resistor
26 - 27
Used with older Snubber
Resistor Braking Kits,
such as the M/N 2DB4010
series, that require a gate
turn-on signal from the
drive.
Table A.5 – Terminal Strip RS-232 Specifications
Signal Type
Terminal(s)
Specification
RS 232 Communications
1
XMIT
2
RECV
3
COMMON