7-14

GV3000/SE AC Drive Hardware Reference, Version 6.06

Table 7.8 - Wiring Signal and Control I/O to the Terminal Strip (Continued)

Terminal

Number

Description

Parameters/Wiring Connections

Wiring a Forward/Reverse Input

19

Digital Input 6

(Default - Forward/Reverse)

Digital input 6 is control function programmable through

parameter P.007. The following parameters must be set:

P.000: Control Source

P.006: Second Menu Password

P.007: Terminal Strip Digital Inputs Configure (Selects and
assigns a control function to digital inputs 6 to 8)

P.008: Terminal Strip Speed Reference Source
(Analog, Motor Operated Potentiometer (MOP), or Preset

Speeds)

P.027: Forward/Reverse Configuration

Note that based on the settings of parameters P.000, P.007,

P.008, and r.030 if an RMI board is used, the following

parameters can affect digital input 6:

P.023: MOP Accel/Decel Time

P.024: MOP Reset Configuration

P.031 to P.038: Preset Speeds 1-8

Refer to the GV3000/SE Software Start-Up and Reference

manual for additional information.

Terminal 19 On = Reverse Direction

Diagram shows factory setting. From the encoder end of the

motor, clockwise rotation indicates forward motor movement.

If P.027 = 1

Forward Direction Only